R.B.L MMI813.1 control box for Riello burner controller

Description

Gas burner automatic safety control

For 2-stage forced draught gas burners

Designated for an air damper control

Possible flame detectors:

- Ionization probe

- Infrared flicker detector

INTRODUCTION

The gas burner automatic safety control MMI 813.1 controls and monitors blown gas- and combined burners of any nominal thermal load (tested and certified according to EN 298).

Together with an air damper motor, a 2-stage burner with 2 fuel valves, a 2-stage operation with 1 fuel valve or a modulating system ave possible.

CONSTRUCTIONAL FEATURES

The automatic control is housed in a non-inflammable, transparent, plug-in type plastic case and contains:

– Synchronous motor with speed reducer gears as the drive for the switching cam

– Switching cam with informative programme display in colour

– 12 times cam drive for controlling the programme sequence

– Plug-in type circuit boards with the electronic components

The following important indicating - and operating elements are located on the front panel of the automatic control:

– Illuminated pushbutton for indication of malfunctions and reset

– Programme display in colour

– Screw for central mounting

TECHNICAL DATA

Operating voltage: 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz)

Differing frequency: results in a proportional deviation of the time.

Rating fuse: max. 10 A rapid, 6 A slow

Power consumption: 10 VA

Max. current per output

term. 3: 2A, cos ϕ 0.2

term. 4, B: 2A, cos ϕ 0.4

term. 5, 6, C: 1A, cos ϕ 0.4

Total load: 5A, cos ϕ 0.4

Amplifier sensitivity: 1 µA

Minimum required

Ionization current: 5 µA

Flame detector cable: max. 20 m cable length

Air pressure monitor: 1 working contact 4 A, 220 V

Waiting time for malfunction remedy: none

Running time air damper for 90°: max. 15 sec.

Flame detector

- Ionization probe

- Infrared flicker detector: IRD 1020

Weight, incl. base: 350 g

Mounting position: any

Insulation standard: IP 44

Admissible ambient temperature for controller and flame detector: -20° C... +60° C

Classification acc. EN 298: BTLLXN